56

IQ 700 Installation Manual

Mode E

One setpoint with preact, dribble control, and tolerance band output
Converts setpoint two (SP2) to be a tolerance output when WT > SP1 – Lo, but < SP1 + HI.
Use the following steps to set Mode E setpoint values

1.

Enter value for

SETPOINT 1

.

2.

Press

SETPOINT 2

3.

Enter desired setpoint value, (display times out if no number is entered for several
seconds).

4.

Press

ENT

key. Display flashes number value alternated with

HI

.

5.

Enter the desired high tolerance value; then press

ENT

key.

6.

Repeat steps for the low tolerance value (Lo) (Low tolerance = SP1 – Lo).

SP1-Pr

SP1-Pr-dr

TOL

ZBD

Mode F

High-Low alarm control
Outputs with low level on when WT < SP1. High level on when WT > SP2.
Use the following steps to set Mode F setpoint values.

1.

Press

SETPOINT 1

.

2.

Enter the desired low level value, (display times out if no number is entered for several
seconds).

3.

Press

ENT

key

4.

Press

SETPOINT 2

.

5.

Enter the desired high level value, (display times out if no number is entered for several
seconds).

6.

Press

ENT

key, display returns to normal operation.

7.

The setpoint value can be recalled any time by pressing the appropriate setpoint key.

LOW

ACCEPT

HIGH

ZBD

Mode

Description

Setpoint

SP1-Pr

-dr

SP1-HI

MODE E

WIRE

PLACEMENT

TB3 - 5

TB3 - 4

TB3 - 3

TB3 - 2

SP1-Lo

SP1-Pr

100

90

80

70

60

50

40

30

20

10

0

WEIGHT

ZBD

MODE F

WIRE

PLACEMENT

TB3 - 5

TB3 - 4

TB3 - 3

TB3 - 2

100

90

80

70

60

50

40

30

20

10

0

WEIGHT

ZBD

LOW

ACCEPT

HIGH