Page 54

AD-4406 Weighing Indicator

15.

15.

15.

15.

Relay Output & Control Input (OP-05)

Relay Output & Control Input (OP-05)

Relay Output & Control Input (OP-05)

Relay Output & Control Input (OP-05)

Replacing the RS-232C interface with this option, 3-relay outputs and 3-control inputs

can be used with the RS-232C interface of this option.

RS-232C functions and pin connections are the same as the RS-232C interface

described in “13. RS-232C Interface (OP-04, OP-05, OP-08)”.

The control inputs can control the indicator from an external terminal just like the front

panel key operations.

Set the external control functions at F13 - F15 of the F-Functions.

When connecting each function pin to the common pin, the indicator makes the action.

Keep a signal width of more than 100 ms for the On-time and Off-time.

ON (Make)

More than 100 ms More than 100 ms

OFF (Break)

The relays output the result of comparison.

Solid-state-relay

Maximum voltage

50VDC

Maximum current

100 mA DC

Maximum resistance 8

W

Pin connections (DIN 8 pin connector)

Function

Pin No.

Signal name

Direction

Description

1

HI

Output

Relay output HI

6

OK

Output

Relay output OK

4

LO

Output

Relay output LO

Relay

output

8

COM (out)

-

Relay common terminal

3

EXT1

Input

Control input 1 (F13)

5

EXT2

Input

Control input 2 (F14)

7

EXT3

Input

Control input 3 (F15)

Control

input

2

COM (in)

-

Control input common

Adaptable connector

JA-TCP0586 (an accessory)

Circuit

HI

OK

LO

COM (out

K

EXT3

EXT2

EXT1

+7

ጚ9V

680

ǡ

680

ǡ

680

ǡ

COM
(in)

DIN connector

of OP-05

Control input

Relay output

15. Relay Output & Control Input (OP-05)