NeoTherm Boilers and Water Heaters

Page 107

Code Description

L or

H

Procedure

97

Internal Fault: A2D mismatch.

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

98

Internal Fault: Exceeded VSNSR

voltage tolerance

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

99

Internal Fault: Exceeded 28V voltage

tolerance

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

100

Pressure Sensor Fault

H

1. Verify the Pressure Sensor is a 4-20 ma source.
2. Check wiring and correct any possible errors.
3. Test Pressure Sensor for correct operation.
4. Replace the Pressure sensor.
5. If previous steps are correct and fault persists,

replace the module.

105

Flame detected out of sequence

H or

L

1. Check that flame is not present in the

combustion chamber. Correct any errors.
2. Make sure that the flame detector is wired to

the correct terminal.
3. Make sure the F & G wires are protected from

stray noise pickup.
4. Reset and sequence the module, if code

reappears, replace the flame detector.
5. Reset and sequence the module, if code

reappears, replace the module.

106

Flame lost in MFEP

L

1. Check main valve wiring and operation -

correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, flame

detector, flame detector siting or flame rod

position.
5. If steps 1 through 4 are correct and the fault

persists, replace the module.

107

Flame lost early in run

L

1. Check main valve wiring and operation -

correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, flame

detector, flame detector siting or flame rod

position.
5. If steps 1 through 4 are correct and the fault

persists, replace the module.