NeoTherm Boilers and Water Heaters

Page 111

Code Description

L or

H

Procedure

159

Main valve OFF

L

1. Check Main Valve terminal wiring and correct

any errors.
2. Reset and sequence the module. If fault

persists, replace the module.

160

Ignition ON

L

1. Check Ignition terminal wiring and correct any

errors.
2. Reset and sequence the module. If fault

persists, replace the module.

161

Ignition OFF

L

1. Check Ignition terminal wiring and correct any

errors.
2. Reset and sequence the module. If fault

persists, replace the module.

164

Block intake ON

L

1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it

is working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the

voltage across the switch. Supply voltage should

be present. If not, the Block Intake Switch is

defective and needs replacing.
5. If the fault persists, replace the relay module.

165

Block intake OFF

L

1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it

is working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the

voltage across the switch. Supply voltage should

be present. If not, the Block Intake Switch is

defective and needs replacing.
5. If the fault persists, replace the relay module.

172

Main relay feedback incorrect

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

174

Safety relay feedback incorrect

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

175

Safety relay open

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

176

Main relay ON at safe start check

L

Internal Fault.
1. Reset Module.
2. If fault repeats, replace module.