5 outdoor installation – LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 18

Advertising
background image

LAARS Heating Systems

Page 14

When an existing boiler is removed from a common

venting system, the common venting system is likely

to be too large for proper venting of the appliances

remaining connected to it.
At the time of removal of an existing boiler,

the following steps shall be followed with each

appliance remaining connected to the common

venting system placed in operation, while the other

appliances remaining connected to the common

venting system are not in operation.
1. Seal any unused openings in the common

venting system.

2. Visually inspect the venting system for proper

size and horizontal pitch and determine there is

no blockage or restriction, leakage, corrosion or

other deficiencies which could cause an unsafe

condition.

3. As much as possible, close all building doors

and windows. Also close all doors between

the space in which the appliances remaining

connected to the common venting system are

located and other spaces of the building. Turn

on any clothes dryers or other appliances not

connected to the common venting system.

Turn on any exhaust fans, such as range hoods

and bathroom exhausts, so they will operate

at maximum speed. Do not operate a summer

exhaust fan. Close any fireplace dampers.

4. Place in operation the appliance being inspected.

Follow the lighting instructions. Adjust the

thermostat so the appliance will operate

continuously.

5. Test for spillage at the draft hood relief opening

after five minutes of main burner operation. Use

the flame of a match or candle, or smoke from a

cigarette, cigar or pipe.

6. After it has been determined that each appliance

remaining connected to the common venting

system properly vents when tested as outlined

above, return the doors, windows, exhaust fans,

fireplace dampers and any other gas burning

appliances to their previous conditions of use.

7. Any improper operation of the common venting

system should be corrected so that the installa-

tion conforms to the National Fuel Gas Code,

ANSI Z223.1/NFPA 54 and/or CSA B149.1,

Installation Codes. When resizing any portion

of the common venting system, the common

venting system should be resized to approach the

minimum size as determined using the appropri-

ate tables and guidelines in the National Fuel

Gas Code, ANSI Z223.1 NFPA 54 and/or CSA

B149.1, Installation Codes.

3.5

outdoor Installation

The NeoTherm unit may only be installed in

applications where the outdoor temperature doesn’t

drop below freezing. For proper operation in

outdoor installations, the boiler must be equipped

with the inlet air and exhaust terminal kits listed in

Table 3C. The bottom panel cover plate must be

removed. Additional instructions are supplied with

the terminal kits.

Advertising
This manual is related to the following products: