NeoTherm Boilers and Water Heaters

Page 83

• On each of the boilers used for DHW, the two

burners in that boiler will operate in Lead/Lag

mode. You can think of each of these boilers

as a separate two-burner Lead/Lag system.

Once a system is set up this way, if there is no DHW

demand, the system will operate like any other

Lead/Lag system. If a demand for DHW arrives,

the boilers used for DHW will stop providing heat

for central heat. On the DHW boilers, the pump(s)

for the DHW loops will start, and those boilers will

provide heat to just the indirect water heaters.
Because this affects an individual boiler, and not the

whole Lead/Lag system, the configuration is done

from outside the Lead/Lag section of the software.

Remember that the boiler includes two controller/

burner combinations. You have to set the DHW

priority on both of the controller/burners.

1. Start at the Home screen. Press the icon for

the controller you want to configure.

2. The Status Summary page for that controller

will appear. Press the Configure button.

3. The system will present the Configuration

screen. Scroll down until you see the line

labeled “DHW Priority vs CH.”

Fig. 116 – DHW Configuration Screen

4. Select that line by pressing it. If you want

to change the DHW priority, the system will

ask you to log in using the installer-level

password. For this kind of installation, the

entry should be “DHW> CH.”

5. Go to the line for “DHW Priority vs Lead

Lag.” For this kind of installation, the entry

should be “DHW> LL.”

6. Remember to change the settings on the other

controller/burner for this boiler.

Setup type 3 –
The third possibility is to set up a single boiler that

just provides domestic hot water. The model NTV

unit is designed for this kind of “volume water”

service. The water is heated as it moves through

the boiler, and that same water is supplied directly

for domestic use. This is really like a conventional

Lead/Lag setup, except priority is given to domestic

hot water, and there is no input for the central

heating function.

• On each boiler which will operate this way,

connect a DHW sensor or the input from the

aquastat to terminals 5 and 6 on TB6. Be

sure there is no thermostat connected (check

terminals 5 and 6 on TB7).

• The two burners in each boiler will operate

in the Lead/Lag mode. You can think of each

boiler as a separate two-burner Lead/Lag

system.

• The setpoint used is the LL DHW setpoint, set

as part of the Lead/Lag system.

• In the Lead/Lag setup, DHW is given priority.

1. From the Home screen (Fig. 117), press the

View Lead Lag button.

fig. 117 – Home Screen