NeoTherm Boilers and Water Heaters

Page 113

Code Description

L or

H

Procedure

196

Invalid ignition source setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

197

Invalid interlock open response setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

198

Invalid interlock start check setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

199

Invalid LCI (Limit Control Input) enable

setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

200

Invalid lightoff rate setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

201

Invalid lightoff rate proving setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

202

Invalid MFEP (Main Flame Establishing

Period) time setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

203

Invalid MFEP (Main Flame Establishing

Period) flame failure response setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

204

Invalid NTC sensor type setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

205

Invalid Outlet high limit response

setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

207

Invalid PII (Pre-Ignition Interlock)

enable setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.