Page 86

Label

Description

How to Reach

CH (Central

Heat) has

priority over

LL (Lead/

Lag)

This controls whether a local Central Heat

demand has priority over the control asserted by

the LL Master, when this controller is enabled as

a slave.

If Lead/Lag enabled –

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen/ Advanced Settings

button/ Domestic Hot Water screen

CH (Central

Heat) I gain

This gain is applied to the Integral term of the

PID equation for the CH loop.

Home screen/ Select controller/ Status

Summary screen/ Configuration button/

Central Heat Configuration/ Arrow keys/

Modulation screen

CH (Central

Heat)

Modulation

Sensor

This selects the sensor used for modulation and

burner demand for the CH loop.

Home screen/ Select controller/ Status

Summary screen/ Configuration button/

Central Heat Configuration/ Arrow keys/

Modulation screen

CH (Central

Heat)

Outdoor

Reset Low

Water

Temperature

This parameter provides the CH Outdoor Reset

setpoint when the outdoor temperature is at

or above the maximum specified by the Max.

Outdoor Temperature.

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen/ Advanced Settings

button/ Left- or Right- arrow buttons/

Outdoor Reset screen

CH (Central

Heat) ODR

(Outdoor

Reset) Max.

Outdoor

Temperature

This parameter determines the maximum

outdoor temperature for the CH outdoor reset

graph. At or above the maximum outdoor

temperature, the water temperature setpoint will

be at the low water temperature.

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen/ Advanced Settings

button/ Left- or Right- arrow buttons/

Outdoor Reset screen

CH (Central

Heat) Off

Hysteresis

The off hysteresis is added to the CH setpoint to

determine the temperature at which the burner

demand turns off.

Home screen/ Select controller/ Status

Summary screen/ Configuration/ Central

Heat Configuration/ Arrow keys/

Modulation screen

CH (Central

Heat) On

Hysteresis

The on hysteresis is subtracted from the CH

Setpoint to determine the temperature at which

the burner demand turns on.

Home screen/ Select controller/ Status

Summary screen/ Configuration/ Central

Heat Configuration/ Arrow keys/

Modulation screen

CH (Central

Heat)

Outdoor

Reset Enable

If outdoor reset is enabled, then the current

outdoor temperature is used to determine

the setpoint by interpolation using the CH

Setpoint (or the CH Time-Of-Day Setpoint if

the Time-Of-Day feature is on), the low water

temperature, and the min. and max. outdoor

temperatures.

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen/ Advanced Settings

button/ Left- or Right- arrow buttons/

Outdoor Reset screen

CH (Central

Heat) P gain

This gain is applied to the proportional term of

the PID equation for the CH loop.

Home screen/ Select controller/ Status

Summary screen/ Configuration/ Central

Heat Configuration/ Arrow keys/

Modulation screen

CH (Central

Heat) Pump

Control

The CH pump (System pump – Pump C) can be

turned on manually, or it can be set to operate

automatically. If it is turned on then it remains

on until changed back to Auto. In Auto mode it

operates according to the demand sources listed

above and the overrun time.

Home screen/ Select controller/ Status

Summary screen/ Configuration/ Pump

Configuration/ Left- or Right- arrow

buttons/ System Pump screen/ Control

Settings button