4 common vent test – LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 17

Advertising
background image

NeoTherm Boilers and Water Heaters

Page 13

3. Locate the combustion air terminal so that it

cannot be blocked by snow. The National Fuel

Gas Code requires that it be at least 12 inches

(30 cm) above grade, but the installer may

determine it should be higher, depending upon

local conditions.

4. If the NeoTherm is side-wall vented to the

same wall, locate the vent terminal at least 1

foot (0.3 m) above the combustion air terminal.

5. Multiple vent kits should be installed such that

the horizontal distance between outlet group

and inlet group is 36” (90 cm). (See Figure 9.)

6. The vent outlet must be at least 12” above the

top of the air inlet, and must be at least 36” (90

cm) horizontally from the air inlet. (See Figure

10.)

3.3.3 Vertical Vent terminal
When the unit is vented through the roof, the vent

must extend at least 3 feet (0.9 m) above the point at

which it penetrates the roof. It must extend at least

2 feet (0.6 m) higher than any portion of a building

within a horizontal distance of 10 feet (3.0 m), and

high enough above the roof line to prevent blockage

from snow. The vent terminal offered with the

NeoTherm can be used in both vertical and horizontal

applications. When the combustion air is taken from

the roof, the combustion air must terminate at least

12” (30 cm) below the vent terminal.

3.3.4 Vertical Combustion air terminal
When combustion air is taken from the roof, a field-

supplied rain cap or an elbow arrangement must be

used to prevent entry of rain water. The opening on

the end of the terminal must be at least 12” (30 cm)

above the point at which it penetrates the roof, and

high enough above the roof line to prevent blockage

from snow. When the vent terminates on the roof, the

combustion air must terminate at least 12” (30 cm)

below the vent terminal.

3.3.5 Installations in the Commonwealth

of massachusetts

In Massachusetts the following items are required

if the side-wall exhaust vent termination is less than

seven (7) feet above finished grade in the area of

the venting, including but not limited to decks and

porches. (From Massachusetts Rules and regulations

248 CMR 5.08.)
1. Installation of Carbon Monoxide Detectors

At the time of installation of the side wall vented

gas fueled appliance, the installing plumber or

gas-fitter shall observe that a hard-wired carbon

monoxide detector with an alarm battery back-

up is installed on the floor level where the gas

appliance is to be installed. In addition, the in-

stalling plumber or gasfitter shall observe that a

battery operated or hard-wired carbon monoxide

detector with an alarm is installed on each addi-

tional level of the dwelling, building or structure

served by the side-wall horizontally vented gas

fueled equipment. It shall be the responsibility

of the property owner to secure the services of

qualified licensed professionals for installation

of hard-wired carbon monoxide detectors.

a. In the event that the side-wall horizontally

vented gas fueled equipment is installed in a

crawl space or an attic, the hard-wired carbon

monoxide with alarm and battery back-up may

be installed on the next adjacent floor level.

b. In the event that the requirements of the sub-

division cannot be met at the time of completion

of installation, the owner shall have a period of

thirty (30) days to comply with the above re-

quirements, provided, however, that during said

thirty (30) day period, a battery operated carbon

monoxide detector with an alarm be installed.

2. Approved Carbon Monoxide Detectors

Each carbon monoxide detector shall comply

with NFPA 720 and be ANSI/UL 2034 listed

and IAS certified.

3. Signage

A metal or plastic identification plate shall be

permanently mounted to the exterior of the

building at a minimum height of eight (8) feet

above grade directly in line with the exhaust

vent terminal for horizontally vented gas fueled

heating appliance or equipment. The sign shall

read, in print no less than one-half (1/2) inch in

size: “GAS VENT DIRECTLY BELOW, KEEP

CLEAR OF ALL OBSTRUCTIONS”.

4. Inspection

The state or local gas inspector of the side-wall

horizontally vented gas fueled appliance shall

not approve the installation unless, upon inspec-

tion, the inspector observes carbon monoxide

detectors and signage installed in accordance

with the provisions of 248 CMR 5.08(2)(a) 1-4.

3.4

Common Vent test

note -This section does not describe a method

for common venting NeoTherm units. It describes

what must be done when a unit is removed from

a common vent system. NeoTherm units require

special vent systems and fans for common vent.

Contact the factory if you have questions about

common venting NeoTherm units.