NeoTherm Boilers and Water Heaters

Page 109

Code Description

L or

H

Procedure

129

Fan speed failed during preignition

H or

L

1. Check wiring and correct any potential wiring

errors.
2. Check the VFDs (Variable-speed Fan Drive)

ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.

130

Fan speed failed during ignition

H or

L

1. Check wiring and correct any potential wiring

errors.
2. Check the VFDs (Variable-speed Fan Drive)

ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.

131

Fan movement detected during standby H

1. Check wiring and correct any potential wiring

errors.
2. Check the VFDs (Variable-speed Fan Drive)

ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.

132

Fan speed failed during run

H

1. Check wiring and correct any potential wiring

errors.
2. Check the VFDs (Variable-speed Fan Drive)

ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.

137

ILK (Interlock) failed to close

H

1. Check wiring and correct any possible shorts.
2. Check Interlock (ILK) switches to assure

proper function.
3. Verify voltage through the interlock string to

the interlock input with a voltmeter.
4. If steps 1-3 are correct and the fault persists,

replace the module.

149

Flame detected

H or

L

Holds if flame detected during Safe Start check up

to Flame Establishing period.

150

Flame not detected

H

Sequence returns to standby and restarts sequence

at the beginning of Purge after the HF switch

opens if flame detected during Safe Start check up

to Flame Establishing period.

152

Combustion pressure ON

H or

L

1. Check wiring and correct any errors.
2. Inspect the Combustion Pressure Switch to

make sure it is working correctly.
3. Reset and sequence the relay module.
4. During STANDBY and PREPURGE, measure

the voltage between J6 terminal 5 and L2 (N).

Supply voltage should be present. If not, the

lockout switch is defective and needs replacing.
5. If the fault persists, replace the relay module.