LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 99

Advertising
background image

NeoTherm Boilers and Water Heaters

Page 95

power supply to the boiler. Turn off all manual gas

valves connecting the boiler to the main gas supply

line. Remove the front door of the boiler to gain

access to the gas valve and Venturi. Disconnect the

four flange bolts connecting the gas manifold pipe

to the gas valve. Remove the electrical connections

to the gas valve. Remove the bolts connecting the

Venturi flange to the blower. This allows the entire

gas valve/Venturi assembly to be removed as an

assembly to facilitate inspection and cleaning.
After the valve has been removed, reassemble in

reverse order making sure to include all gaskets and

O-rings. Turn on the manual gas valves and check

for gas leaks. Turn on the 120 Volt power. Place the

unit in operation following the instructions in Section

10. Once the boiler is operating, check for leaks

again and confirm all fasteners are tight.
Check the setup for the unit according to the

instructions in Section 9.

11.2.3 Controllers
Each NeoTherm unit has two integrated controllers

that incorporate manual reset high limit control,

operating temperature control, modulating control,

ignition control, outdoor reset control, pump control

and many other features. If any of these features are

thought to be defective, please consult the factory for

proper troubleshooting practices before replacing a

control.
If it is necessary to replace a controller, turn off

all power to the unit and shut off all manual gas

valves to the unit. Remove the front door to the

unit and the control panel plastic bezel. Remove

all wire connections from the control board. The

control board connections are keyed to only allow

connection in the proper location, but proper

handling techniques should be used to avoid damage

to the wiring or connectors. To remove the control,

undo the mounting screws. To replace the control

repeat the steps listed above in the reverse order

making sure to connect all wires in the proper

locations. Place the unit in operation following the

steps outlined in Section 10.

11.2.4 Ignitor assembly
The ignitor assembly is a two rod system that

consists of a ground rod and a sense rod. To remove

the ignitor assembly, shut off the 120 Volt power

supply to the unit. Turn off all manual gas valves

connecting the unit to the main gas supply line.

Remove the front door of the boiler to gain access

to the ignitor assembly. Remove the two wires

connected to the assembly. Then remove the two

bolts connecting the ignitor assembly to the burner

door. Remove and replace the old ignitor assembly

gasket. If the old assembly is determined to be

defective, install a new ignitor assembly in the

reverse order. Replace the gasket if necessary.

11.2.5 flame Sensor
The flame sensor is a single rod system. To replace

the flame sensor electrode, shut off the 120 Volt

power supply to the boiler. Turn off all manual gas

valves connecting the boiler to the main gas supply

line. Remove the front door of the boiler to gain

access to the flame sensor electrode. Remove the

flame sensor wire from the electrode. Remove the

two bolts fastening the electrode to the burner doors.

Remove and replace the old flame sensor gasket.

If the old electrode is determined to be defective,

reinstall a new flame sensor electrode in the reverse

order.

Caution

The igniters and sensors get become very hot. If

you touch these parts accidentally, this can cause

burns or injury.

11.2.6 transformer with Integral Circuit

Breaker

The appliance has a 24 VAC transformer with

integral 4 amp circuit breaker installed for supplying

the control voltage required for the unit only. The

transformer is sized for the load produced by the

unit only and should not be used to supply power

to additional field devices. If additional loads are

added or a short occurs during installation, the

integral circuit breaker may trip. If this happens, be

sure to reset the circuit breaker before replacing the

transformer.
If the transformer must be replaced, turn off the 120

VAC power to the unit. Remove the transformer

wires from the terminal blocks. Remove the

fasteners holding the transformer, and remove the

transformer. Replace with a new transformer in

reverse order.
If the transformer is replaced with a part other

than the OEM transformer, be sure to add circuit

protection if it is not integral to the new transformer.

WarnInG

Failure to include proper circuit protection may

lead to premature component failure, fire, injury or

death.

Advertising
This manual is related to the following products: