2 connection terminals, Laars heating systems – LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 50

Advertising
background image

LAARS Heating Systems

Page 46

fig. 51 – lead/lag activity in a multi-Boiler

System

Low demand -
The first burner* in
sequence fires at
less than 65%

First
burner*

Second
burner*

Third
burner*

Fourth
burner*

Boiler X

Boiler Y

Demand increases -
Once the first burner
reaches 50%,
the second burner*
switches on, and
both modulate
together between 29%
and 65%

Demand increases -
Once the first two
burners reach 65%,
the third burner*
switches on, and all
three modulate together
between 29% and 65%

Nearing max. demand -
The fourth burner* is
active. Once all four
reach 65%, all are
allowed to go over
65%

* - The Lead/Lag controller will change the firing order of the
burners, based on the run time of each burner.

9.1.3

ntH lead/lag with Indirect

Domestic Hot Water

So far, we have been describing a system which

handles the Central Heat function only. There are

several ways the Domestic Hot Water can be set up

on a Lead/Lag system. For a detailed description,

see Section 9.5.

9.2

Connection terminals

Figure 52 shows some of the connection terminals

on the circuit board inside the cabinet.

WarnInG

Before connecting or disconnecting any wiring

inside a boiler, be absolutely sure to turn off all

electrical power to the unit. Failure to do this

could result in property damage, serious injury or

death.