LAARS Heating Systems

Page 84

2. If the system was running, the following

screen would normally show the current

activity of each unit in the multiple boiler

arrangement. See Fig. 118.

fig. 118 – lead/lag Screen

3. Press the button for Lead Lag Master. Fig.

119 shows the screen that follows.

fig. 119 – lead/lag master Screen


4. Press the Configure button. The display will

present the Lead/Lag Master Configuration

Screen (Fig. 120).

Fig. 120 – Lead/Lag Master Configuration

Set the DHW setpoint on this screen.

5. Press the button for Advanced Settings. This

leads to a “ring” of related screens, and you can

scroll through the list by pressing one of the

left- or right-arrow symbols. Press the left-

arrow or right-arrow until you see the Domestic

Hot Water screen (Fig. 121).

fig. 121 – Domestic Hot Water

Set the last line to give priority to the DHW

function.