NeoTherm Boilers and Water Heaters

Page 117

12.4 Diagnostic tests and Input/

output Indicators

Two kinds of screens are grouped together in this

section:

Detailed indications of the input and output

signals

Diagnostic tests of the pumps and burner

modulation

Note that these functions apply to just one selected

controller.

How to get there –

Home Page <Select icon> Status Summary Screen

<Diagnostics button>

1. The first screen in the sequence lists digital

inputs and outputs. These are signals that are

either “on” or “off.” See Fig. 132.

fig. 132 - Digital I/o Screen

A green dot indicates a function that is “on.”

There is too much information to appear on

one screen. Use the left- and right-arrows to

see the rest of the list.

2. Press the Analog I/O button to look at

functions where the values move continuously

between two limits. See Fig. 133.

fig. 133 – analog I/o Screen

3. Press the button for Diagnostic Tests. The

Modulation test allows you to change the

rate at which the burner fires, and watch the

results. See Fig. 134.

fig. 134 – modulation test

4. On the screen for the Modulation Test, press

the Pump Test button. The Pump test shows

detailed information on the activity of the

three pumps that may be used by the system.