11

FIGURE 4-1 Clearance to Combustible Materials

TABLE 2: BOILER CLEARANCES

Dimension

Combustible

Materials

(1)

Service

(1)(2)

Model 050/075/100/

150/200/299

050/075/100/

150/200/299

Top (A)

0" (0 cm)

14" (36 cm)

Left Side (B)

0" (0 cm)

0" (0 cm)

Right Side (C)

0" (0 cm)

0" (0 cm)

Front (D)

0" (0 cm)

6" (16 cm)

Back (E)

0" (0 cm)

0" (0 cm)

Bottom (F)

0" (0 cm)

12" (32 cm)

Combustion Air/Vent

piping

0" (0 cm)

6" (16 cm)

Hot Water Piping

See local code

6" (16 cm)

(1)

Required distances measured from boiler jacket.

(2)

Service, proper operation clearance recommendation.

A

E

E

D

A

C

B

A

F L O O R

F L O O R

F

F

F

F

4.1 Boiler Location Considerations

• Ambient room temperature always above 32°F (0°C) to

prevent freezing of liquid condensate.

• Approved for installation in closets.
• Protect gas ignition system components from water

(dripping, spraying, rain, etc.) during operation and

service (circulator replacement, condensate trap, control

replacement, etc.).

• Wall mount only.
• Access to outdoors to meet minimum and maximum

pipe lengths for combustion air and vent piping. See

section 6.

• Disposal of condensate. See section 6.
• Drainage of water (or water - antifreeze solution) during

boiler service or from safety relief valve discharge. See

section 5.

• Access to system water piping, gas supply, and electrical

service. See sections 5, 7 and 8.

• Clearances to combustible materials and service

clearances. See Table 2 and figure 4-1.

• Multiple Boilers can be wall mounted, placed side by

side,

or

back to back.

4 - LOCATING BOILER