5.1 General

• Install piping in accordance with authority having jurisdiction.

NOTICE

Use two (2) wrenches when tightening and fitting

to pipe boiler's threaded fittings. Boiler's internal

piping can be damaged if subjected to excessive

torque.

• Support system piping and safety relief valve discharge

piping. Boiler's internal piping and wall mount bracket can

be damaged if subjected to excessive weight.

• Size central heating pump (and domestic hot water

pump, if used) for system requirements only. Internal

heat exchanger pump compensates for pressure drop

through boiler internal piping and heat exchanger.

• Thoroughly clean and flush system before connecting to

boiler.

• If oil is present in system water, use approved detergent to

wash system.

• Flush system to remove any solid objects such as metal

chips, fibers, or Teflon tape, etc.

5.2 Special Conditions

• System piping exposed to freezing conditions: Use

inhibited propylene glycol solutions certified by fluid

manufacturer for use with closed water heating system.

Do not use automotive or ethylene glycol.

• Boiler installed above radiation level (or as required by

authority having jurisdiction). Integral low water cutoff

provided in boiler. See pages 9 & 10.

• Boiler used in connection with refrigeration system.

Install piping in parallel with boiler, with appropriate

valves to prevent chilled medium from entering boiler.

• System piping connected to heating coils located in air

handling unit exposed to refrigerated air circulation. Install

flow control valves or other automatic means to prevent

gravity circulation of boiler water during cooling cycle.

5.3 Safety Relief Valve and Air Vent

NOTICE

Boiler rated at 150 psig (1.03 MPa) maximum

allowable working pressure. Boiler provided with

30 psig (206 kPa) safety relief valve. Field source

safety relief valve for system pressures greater

than 25 psig. Temperature Pressure Gauge and Air

Vent satisfactory for 75 psig operation. Field source

temperature pressure gauge for system pressures

greater than 60 psig.

• Install safety relief valve and air vent using pipe fittings

provided with boiler. See figure 5-1

• Install safety relief valve with spindle in vertical position.
• Do not install shutoff valve between boiler and safety

relief valve.

WARNING

• Poison hazard. Ethylene glycol is toxic. Do not

use ethylene glycol.

• Never use automotive or standard glycol antifreeze,

even ethylene glycol made for hydronic systems.

• Ethylene glycol can attack gaskets and seals used

in hydronic systems.

• Use only inhibited proplyene glycol solutions

certified by fluid manufacturer as acceptable for

use with closed water heating system.

• Thoroughly clean and flush any system that used

glycol before installing new Boiler.

• Provide user with Material Safety Data Sheet

(MSDS) on fluid used.

!

NOTICE

Do not expose boiler and condensate piping to

freezing temperatures.

FIGURE 5-1 Safety Relief Valve & Air Vent (Viewed

from front of boiler)

Safety Relief

Valve

3/4" NPT

Nipple

3/4" x 1/4" NPT

90° Elbow

3/4"F x 3/4"M

NPT Tee

3/4 NPT

Air Vent

Position Air Vent and Safety Relief Valve

to provide space for discharge piping.