User Interface Display

Explanation

Sett

ings

Setting Range: 104° F to 195° F (40° C to 91° C)

Default Value: 140° F (60° C)

Adjust CH set point to hydronic system design while in

Operating in CH Mode = 0 (CH with Thermostat) or 3

(Permanent Demand).

In CH Mode = 1 (CH with Thermostat and Outdoor Reset) or 2

(CH with Full Outdoor Reset). Display will change to ‘OD Reset

Setpoint’ and cannot be changed. Controller calculates set point

based on outdoor temperature.

Note: For explanation of available CH heating modes,

refer to ‘CH Mode’ section located in ‘CH Settings’

submenu in Installer Menu.

Setting Range: 104° F to 195° F (40° C to 91° C)

Default Value: 180° F (82° C)

DHW set point determines supply water temperature set point

while operating in DHW mode.

User interface temperature unit of measure is selected using

‘Change Temperature Units’ screen.
Fahrenheit and Celsius available.

APPENDIX A - CONTROL MODULE