Dunkirk Helix VLT Vertical Laser Tube, Wall Hung Modulating Condensing Boiler User Manual

Page 72

Advertising
background image

72

1.4 Sequence of Operation

Operational State

User Interface Display

Explanation

If flame detected before Gas Valve opens

during ignition boiler will lockout.
Please refer to troubleshooting guide.

Gas Valve energized to deliver air/fuel to

burner.

If flame undetected after 3 seconds boiler

will de-energize Gas Valve and enter post

purge mode for 30 seconds.
Ignition attempted 5 times before

lockout.

Boiler will run provided all operational

and safety devices are within limits
Refer to for more information.
Control module adjusts firing rate

according to heating demand. When

Boiler detects demand met, will enter

post purge mode then standby mode.

If simultaneous demand for Central Heat

and DHW, boiler will enter DHW Priority

Mode.
Priority mode limits amount of time

boiler can run in DHW mode to meet CH

demand.
Max DHW Priority Time setting

determines maximum time allowed for

DHW heating mode.
Please refer to section Appendix A section

1.5 for more information.

Flame

Detected?

Gas Valve

Energized

Flame

Detected?

Heat Demand

Met?

DHW

Priority

Mode

Simultaneous

DHW + CH

Demand?

No

Yes

No

Yes

See Max DHW

Priority Time

Setting

No

After 2 seconds

After 3 seconds

No

30 second

post purge

Yes

Yes

Lockout

Error A21

Note:

5 Ignition

trials,

then

Lockout A01

APPENDIX A - CONTROL MODULE