29

Multiple

Family

Dwellings

Vent shall not terminate directly above

paved sidewalk or paved driveway located

between two single-family dwellings serving

both dwellings.

7' (2.1m)

Minimum

3' (0.9m)

Minimum

Termination

Stones,

Balls, Etc.

Position combustion air and vent

termination where it will NOT be damaged by

foreign objects, such as stones, balls, etc.

People or

Pets

Locate combustion air and vent termination to

prevent accidental contact with people or pets.

Eddy, Flue

Gases

Position termination so it will not be

effected by wind eddy, air born leaves,

snow, or recirculated vent gases. Give

consideration to excessive wind and locate

away from windward side of building.

Vapors

Position termination where vent vapors are

not objectionable.

Walkways

Locate vent termination minimum 7'

(2.1m) above any public walkway, with

consideration to condensate.

Meters,

Regulators,

deck, porch

Vent termination US only - 4’ (1.2m),

Canada - 6' (1.9m) horizontally from,

no case above or below, electric meters,

gas meters, regulators, and relief

equipment, or under deck or porch.

Vegetation,

Plants &

Shrubs

Keep vent termination 3’ minimum

(0.9m) away from vegetation. Position

termination where vent vapors will not

damage plants/shrubs or air conditioning

equipment.

FIGURE 6-15

FIGURE 6-16

6 - COMBUSTION AIR AND VENT PIPING