12.1 Ratings and Capacities

• Constructed and hydrostatically tested for maximum

allowable working pressure of 50 psig (pounds per

square inch gauge) (345 kPa) in accordance with ASME

Boiler and Pressure Vessel Code, Section IV, Rules for

Construction of Heating Boilers.

• Ratings used for elevations up to 2000 ft (600m) above

sea level.

• For elevations between 2000 ft (600m) and 4500 ft

(1350m), install high altitude control kit

• For elevations above 4500 ft (1350m) install high

altitude control kit and :

• USA - Reduce input rate 4% for each 1000 ft

(300m) beyond 4500 ft.

TABLE 12-1: SEA LEVEL RATINGS

NATURAL AND PROPANE GASES

Size

Boiler Input Rate (MBH)

(1)

Heating Capacity

(MBH)

(1)(2)

Net AHRI Rating,

Water (MBH)

(1)(3)

AFUE

(2)

Maximum

Minimum

050

50

10

46

40

95.0

075

75

15

69

60

95.0

100

100

20

91

79

95.0

150

150

30

139

121

95.0

200

200

40

185

161

95.0

299

299

60

273

239

95.0

(1)

1000 Btu/hr (British Thermal Units Per Hour)

(2)

procedures.

(3)

Net AHRI Ratings based on piping and pickup allowance of 1.15. Contact Technical Support before selecting boiler for

installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems,

etc.

12 - RATINGS AND CAPACITIES