7.1 General

• Use piping materials and joining methods acceptable

to authority having jurisdiction. In absence of such

requirements:

• USA - National Fuel Gas Code, ANSI Z223.1/NFPA

54

• Size and install gas piping system to provide sufficient

gas supply to meet maximum input at not less than

minimum supply pressure. See Table 10.

• Support piping with hooks straps, bands, brackets,

hangers, or building structure components to prevent or

dampen excessive vibrations and prevent strain on gas

connection. Boiler will not support piping weight.

• Use thread (joint) compound (pipe dope) suitable for

liquefied petroleum gas.

• Provide sediment trap up stream of gas valve.
• Install manual main shutoff valve outside of jacket. See

figure 7-2.

7.2 Conversion Kit Instructions

• See Gas Conversion Kit Instructions included with Boiler.

Table 10 -

Gas Supply Pressure

FIGURE 7-2 Manual Main Gas Shutoff Valve Outside

Boiler Jacket

7.3 Leak Check Gas Piping

Pressure test boiler and gas connection before placing

boiler in operation.

• Pressure test over 1/2 psig (3.5 kPa). Disconnect

boiler and its individual gas shutoff valve from

gas supply system.

• Pressure test at 1/2 psig (3.5 kPa) or less.

Isolate boiler from gas supply system by closing

manual gas shutoff valve. See figure 7-2.

• Locate leakage using gas detector, noncorrosive

detection fluid, or other leak detection method

acceptable to authority having jurisdiction. Do

not use matches, candles, open flames, or other

methods that can provide ignition source.

• Correct leaks immediately and retest.

Manual Main Gas

Shutoff Valve

FIGURE 7-3 Gas Shutoff Valve - 050/075/100/150/200

DANGER

Fire Hazard. Do not use matches, candles, open

flames, or other methods providing ignition source.

Failure to comply will result in death or serious

injury.

!

Gas shutoff valve

(shown in closed

position)

FIGURE 7-4 Gas Shutoff Valve - 299

Gas shutoff valve

(shown in open

position)