Warning – Dunkirk Helix VLT Vertical Laser Tube, Wall Hung Modulating Condensing Boiler User Manual

Page 21

Advertising
background image

21

6.1 General

This boiler requires a dedicated direct vent system.

Install combustion air and vent piping in accordance

with these instructions, authority having jurisdiction,

and:

• USA - National Fuel Gas Code, ANSI 223.1/NFPA 54.

Vent connections serving appliances vented by natural draft

shall not be connected into any portion of mechanical draft

systems operating under positive pressure.
Install vent system in accordance with these instructions.

6.2 Removal of Existing Boiler From Common

Vent System

When existing boiler is removed from common venting

system, common venting system is likely to be too large for

proper venting of appliances remaining connected to it.
After removal of existing boiler, following steps shall

be followed with each appliance remaining connected to

common venting system placed in operation, while other

appliances remaining connected to common venting system

are not in operation:

• Seal any unused openings in common venting system.
• Visually inspect venting system for proper size and

horizontal pitch. Determine there is no blockage or

restrictions, leakage, corrosion and other deficiencies

which could cause an unsafe condition.

• When practical, close all building doors, windows, and

all doors between space in which appliances remaining

connected to common venting system are located

and other spaces of building. Turn on clothes dryer

and any appliance not connected to common venting

system. Turn on exhaust fans, such as range hoods and

bathroom exhaust so they will operate at maximum

speed. Do not operate summer exhaust fan. Close

fireplace dampers.

• Turn on appliance being inspected. Follow lighting

instructions. Adjust thermostat so appliances will operate

continuously.

• Test for spillage at draft hood relief opening after 5

minutes of main burner operation. Use flame of match or

candle, smoke from cigarette, cigar or pipe.

• Determine each appliance remaining connected to

common venting system properly vents when tested

as outlined above. Then return doors, windows,

exhaust fans and any other gas-burning appliance to

their previous condition of use.

• Any improper operation of common venting system

should be corrected so installation conforms with National

Fuel Code, ANSI Z223.1/NFPA 54 and/or Natural Gas

and Propane Installation Code, CAN/CSA B149.1.

When re-sizing any portion of common venting system,

common venting system should be re-sized to approach

minimum size as determined using appropriate tables in

Chapter 13 of the National Fuel Gas Code, ANSI Z223.1/

NFPA 54 and/or Natural Gas and Propane Installation

Code, CAN/CSA B149.1.

6.3 Venting Materials

• See Table 4

Table 4 - Combustion air and vent pipe fittings

must conform with the following:

Item

Material

Standards

Vent Pipe

and Fittings

PVC schedule 40

ANSI/ASTM D1785

PVC - DWV

ANSI/ASTM D2665

CPVC schedule 40

ANSI/ASTM D1784/

F441

SDR-21 & SDR-26 PVC

ANSI/ASTM D2241

ABS-DWV

ANSI/ASTM D2661

Schedule 40ABS

ANSI/ASTM F628

PP (Polypropylene)

Pipe and Components

UL 1738

ULC S636-08

Pipe

Cement/

Primer

PVC

ANSI/ASTM D2564

CPVC

ANSI/ASTM F493

Schedule 40 ABS

ANSI/ASTM D2235

• IPEX is approved vent manufacturer in Canada listed

to ULC-S636.

• IPEX System 636 Cements and Primers are approved

in Canada listed to ULC-S636.

Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel

®

,

(Polyphenolsulfone) in venting systems shall be prohibited.

WARNING

Use of cellular core PVC for venting flue gas could

result in death, or serious injury.

!

6 - COMBUSTION AIR AND VENT PIPING

WARNING

Covering non-metallic vent pipe and fittings with

thermal insulation shall be prohibited.

Advertising