User Interface Display

Explanation

Installer Menu

Bo

iler Status

Control module logs successful and failed ignition attempts.

Information accessed in ‘Ignition Attempts’ Screen as shown.
Ignition attempts are stored in non-volatile memory and are

retained in event of power failure.
Figure A-1 Typical Ignition Cycle

Following control features are implemented to ensure safe and

reliable operation of Combustion System:

False Flame

Detection

If flame is detected at end of pre-spark

period (Ignit_0) than lockout will occur.

Re-ignition

If at end of safety period no flame detected

control will go to post-purge removing

unburned gas. Re-ignition attempt started

following same cycle. Number of re-ignition

attempts limited to 3 after which lockout

occurs.

Intermittent

Operation

Boiler can be firing continuously for 24

hours. Burner switched off and restart

sequence follows.

Flame out too

late

If flame detected after post purge lockout

follows.

Safety relay test In Safety ON/OFF state correct operation

of safety relay is proved before ignition.

UL3563

High Limit

Temperature

Device

Boiler comes equipped with UL353

approved temperature high limit device.
Gas Valve de-energized when supply

temperature exceeds 203°F lockout

follows.

APPENDIX A - CONTROL MODULE