Dunkirk Helix VLT Vertical Laser Tube, Wall Hung Modulating Condensing Boiler User Manual

Page 50

Advertising
background image

50

13 - TROUBLE SHOOTING

_ _ _ _

_

Lockout Alarm A 0 0 Blocking too long e

rror

Enter Installer Menu, Boil

er

Status. Scr

oll

to

most recent

Lockout Alarm or Blocking Error. Di

agnose corrective action usi

ng

appropriate Trou

blesh

ooting Tree.

Unplug connector on supply

sensor

. Measure continuit

y of high

limit sensor (close/open signal) between two pins connected to two purple wires. Is continuit

y

av

ailable?

NO

YES

Is wire harness connected to both Gas V

alv

e and J13

connector on Control

Module?

NO

YES

Disconnect J13 connector on Control Module. Measure resistance across third (blue wire) and fourth (brown wire)

terminals. Is resistance between 1.0 and 1.2 k

Ω?

NO

YES

Disconnect harness from Gas V

alv

e. Does each

wire ha

ve continuit

y

between Gas V

alv

e and

Control Module

NO

YES

Is supply pipe (copper pipe at top of boiler)

hot?

NO

YES

Boiler has been dry fired. S

ystem has too

much air

. Close manual

gas v

alv

e (shut off gas).

Purge air from system, wait for system to cool.

Replace Supply Sensor

Connect harness

Replace Control

Module

Replace Gas V

alv

e

Replace Harness