Ch set tings, Explanation, 80 user interface display – Dunkirk Helix VLT Vertical Laser Tube, Wall Hung Modulating Condensing Boiler User Manual

Page 80: Ac d appendix a - control module

Advertising
background image

80

User Interface Display

Explanation

CH Set

tings

Allowed Range: 35°F to 100°F (2°C to 38°C)

Default Setting: 70°F (21°C)

If outdoor temperature is greater than Warm Weather

Shutdown Temperature, demand for CH blocked and pumps

stopped.

Allowed Boiler Range: 60°F to 195°F (40°C

to 91°C)
Default Boiler Setting:180° F (82°C)

Boiler capable of operating in Outdoor Reset Mode when

included Outdoor Sensor is connected and proper CH Mode

selected.
If CH Mode = 1, ‘Outdoor Temperature Reset with

Thermostat’ or 2, ‘Full Outdoor Reset’ boiler will adjust

CH set point proportional to outdoor temperature as

Outdoor reset curve adjusted by modifying Design and Mild

Weather reference temperatures. See points A & B of Reset

Curve below.
Calculated CH set point always limited between ‘Reset Curve

Boiler Minimum/Maximum’ temperatures. See points C & D

of Reset Curve below.
Figure A-2 Outdoor Reset Curve

Calculated supply temperature follows thick black line in

graph below based on outdoor temperature.

Note:

• Modes only function when outdoor temperature sensor

connected.

• If ‘Open’ outdoor sensor detected CH set point equal to

‘Boiler Reset Curve Design’ temperature.

• Outdoor temperature used for CH set point calculation

measured once a minute and averaged with

previous measurement to compensate for rapid outdoor

temperature variations.

Allowed Min. Range: 40°F to 180°F (4°C to 82°C)

Default Min. Setting: 70°F (21°C)
Allowed Max. Range: 80°F to 195°F (27°C to 91°

C)

Default Max. Setting: 180°F (82°C)

B

Allowed Boiler Range: 35°F to 120 F (2°C to

49°C)

Default Boiler Setting: 100°F (37°C)
Allowed Outdoor Range: 35°F to 85°F (2°C to

29°C)

Default Outdoor Setting: 70°F (21°C)

1 0 0

A

C

D

APPENDIX A - CONTROL MODULE

A

B

D

C

80

100

120

140

160

180

200

220

0

20

40

60

80

100

Outdoor Temperature F

Supp

ly

T

em

pe

ra

tu

re

S

et

po

in

t

F

Reset Curve Design Points , A and B,

define a straignt line.

Boiler Min and Max, C and D, define a

section on the straignt line.

Boiler supply temperature Setpoint

follows the bold line sections

Outdoor Temperature

°F

Suppy Temperature Setpoint

°F