6.9 Condensate Piping

• Use materials acceptable to authority having jurisdiction.

In absence of such authority:

• USA - PVC or CPVC per ASTM D1785/D2845 Cement

or primer per ASME D2564 or F493.

• Canada - CSA or ULC certified PVC/CPVC pipe,

fittings and cement.

• Attach PVC tee provided with boiler and field sourced

piping to condensate drain at bottom of boiler. See

figure 6-18.

• Slope condensate drain pipe minimum 1/4" per foot

(21mm/m) away from boiler.

• Use field source condensate pump if boiler located

below disposal point.

• Field source condensate neutralizing kit as required

by authority having jurisdiction or for environmentally

friendly condensate disposal.

FIGURE 6-18 Condensate Drain

Condensate Tee

(field installed)

on condensate drain pipe

Do not glue cap on if used

for dust protection. End

must be left open.

Do not place in environment with

temperatures below freezing.

Condensate outlet will block if

condensate freezes.