Dunkirk Helix VLT Vertical Laser Tube, Wall Hung Modulating Condensing Boiler User Manual

Page 37

Advertising
background image

37

9 -2 User Interface

9.3 Program Boiler Control

Key

Description
- Manual Lockout Reset
- Enter/Exit user menu

- Go to previous screen
- Select a menu item

- Confirm new parameter value
- Scroll up to next menu item

- Increase value
- Scroll down to next menu item

- Decrease value

Boiler is factory programmed with following factory

default settings, Table 11.
Parameters can be adjusted to suit particular application

using the user interface. See figure 9-2.
Detailed explanation of each can be found in Appendix

A - Control Module.
List parameters in event of factory default parameters are

changed.

9-3 Default Table

Control Parameter

Factory Default

Setting

Setting Range

*Actual

Parameter

Settings

Standard

Metric

Standard

Metric

User

Menu

Settings

Central Heating Setpoint

140°F

60°C

104-195°F 40-91°C

DHW Setpoint

180°F

82°C

104-195°F 40-91°C

Temperature Units

°F

°F/°C

Installer

Menu

Boiler

Configuration

Boiler Address

0

0-15

Low Water Cutoff

Enabled

Enable/Disabled

Pump Mode

0

0 & 4

Service Reminder Status

On

ON/OFF

Service Reminder Days

365 Days

1- 999 Days

CH Settings

CH Mode

1

0, 1, 2, 3

Warm Weather Shutdown

70°F

21°C

35-100°F

2-38°C

Reset Curve Design Temperature - Boiler

180°F

82°C

60-195°F 40-91°C

Reset Curve Design Temperature - Outdoor

25°F

-4°C

-60-32°F

-51-

25°C

Reset Curve Mild Weather Temperature - Boiler

100°F

37°C

35-120°F

2-49°C

Reset Curve Mild Weather Temperature - Outdoor

70°F

21°C

35-85°F

2-29°C

Reset Curve Boiler Minimum Temperature

70°F

21°C

40-180°F

4-82°C

Reset Curve Boiler Maximum Temperature

180°

82°C

80-195°F 27-91°C

Boost Function Temperature

0°F

0°C

0-36°F

0-20°C

Boost Function Time

20 Minutes

1-120

Maximum Power CH

100%

1-100%

DHW Mode

0

0/2

DHW Maximum Priority Time

30 Minutes

1-60 minutes

* List parameters in event of Control Module Failure to reprogram your settings.