APPENDIX C - SYSTEM MANAGER TS ALARM POLLING

Prism 2 Technical Guide

42

Setting Up Alarm Polling for the System Manager TS

Revised 8/29/11

Setting Up Alarm Polling for the

System Manager TS

NOTE:

This section applies to System Manager Touch Screen

Alarm Polling only. For Prism 2 Alarm Polling, see Section 9.

Using Prism 2 to set up Alarm Polling for the System Manager
TS, you must have a CommLink and MiniLink Polling Device
installed on your system. The following procedure must be done
for the MiniLink Polling Device on each loop.

In the Loop Selection Window of the Prism
2 Main Screen, select
the loop where your
MiniLink Polling Device is located. Then,
in the Unit Selection Window scroll down to
Address 60 - MiniLink PD and click once
on your selection.

Click the

<Alarm Polling>

option at the top far right of the Polling

Device Setpoints Window. The Alarm / Override Polling Window
will appear.

In the Alarm / Override Polling Window, click the box to the left of
each controller to choose alarm polling and push-button overrides
for that controller. A check mark in the box designates alarm
polling/push-button override.

The Polling Device Window will appear.

Click

<Setpoints>

at the top of the screen. The Polling Device

Setpoints Window will appear.