Operation Section
11
3.5 Air Flow
• Air drawn from the right side face passes through the condenser which extracts the heat. This
hot air is blown out through the upper exhaust air duct. Air taken in from the front face is cooled
by the evaporator and then blown through the cool air vent. All the air inlets are equipped with
filters, and the exhaust air duct is protected by metal grill.
3.6 Electrical System
• The MovinCool Office Pro 63 is equipped with a compressor operated at 460 V, 3 phase and a
dry-type distribution transformer operated 460 V, single phase at primary side and 230 V single
phase at secondary side which supply power source for fan motors, relay board, and
condensate pump.
3.7 Compressor and Fans
• The compressor is hermetically sealed. Two sets of a two-speed fan motor with a centrifugal fan
are used to draw air across the evaporator and condenser.
3.8 Transformer
• The transformer is a dry-type distribution transformer rated 5 KVA at 460 V primary side and
230 V secondary side.
I001909
Condenser Air In
Evaporator Air In
Exhaust Air Out
Cool Air Out