5 fan motor, Fan motor – MovinCool Office Pro 63 Service Manual User Manual

Page 25

Advertising
background image

Operation Section

25

(5) Fuse (For Transformer)

• This fuse provides protection against damage

to the transformer. The fuse is located in the

secondary circuit of the transformer.

• It must be replaced with the exact type of fuse

or an equivalent.

Specifications:

- Time delay type

- Class cc

- Rated volt: 600 V

- Rated amp: 15 A

- UL listed

6.5 Fan Motor

(1) For evaporator

• The fan motor is a single phase, induction type

two-speed motor.

Specifications:

- Rated Voltage: 230 V, 60 Hz

- Rated Output: High-590 W, Low-360 W

(2) For condenser

• The fan motor is a single phase, induction type

two-speed motor.

Specifications:

- Rated Voltage: 230 V, 60 Hz

- Rated Output: High-1195 W, Low-932 W

I001956

Fuse

Control Box

I001774

Evaporator Fan Motor

Ground (Green/Yellow)

J7 Low (Red)

CF22 (Brown/White)

CF21 (White)

J8 High (Black)

I001775

Condenser Fan Motor

Ground (Green/Yellow)

J5 Low (Red)

CF12 (Brown/White)

CF11 (White or Orange)

J6 High (Black)

Advertising