(3) Overflow of drain water

Symptom

Possible Cause

Remedy

Checking Area

Cause

Stops

immediately

after

starting

Control

panel

display

normally.

1. Fan on-off relay on the relay

board.

Open circuit or insufficient

contact.

Replace relay board.

2. Fan HI/LO change relay on

the relay board.

Open circuit or insufficient

contact.

Replace relay board.

3. Fan motor insulation

resistance.

Insulation failure on fan

motor.

Replace fan motor.

4. Compressor relay.

Open circuit or insufficient

contact.

Replace compressor

relay.

5. Compressor relay on the

relay board.

Open circuit or insufficient

contact.

Replace relay board.

6. Compressor insulation

resistance.

Insulation failure on

compressor.

Replace compressor.

7. Reverse phase protector.

Open circuit or insufficient

contact.

Replace reverse phase

protector.

Stops after

running a

while

Control

panel

display

normally.

1. Temperature of fan motor

(abnormally high).

Operation of safety device

(IOLF) due to fan motor

malfunction.

Replace fan motor.

2. Temperature of compressor

(abnormally high).

Operation of safety device

(IOLC) due to compressor

malfunction.

Replace compressor.

3. Refrigerant leakage.

Insufficient refrigerant or gas

leakage.

Repair and charge

refrigerant.

4. Dirt on evaporator or

condenser.

Insufficient cooling of

evaporator or condenser.

Clean evaporator or

condenser.

5. Duct connection state.

Improper connection.

Repair duct connection.

Symptom

Possible Cause

Remedy

Checking Area

Cause

Overflow from the unit.

1. Drain pan.

Cracks in drain pan.

Check and repair.

2. Water level in drain pan.

Clogged drain hose.

Check and replace.

3. Drain hole.

Reversed air flow from drain

hole.

Insert a trap on discharge

drain hose.

4. Clogged air filter.

Reversed air flow from drain

hole due to the excessive

negative pressure inside of

the unit.

Clean air filter.