Operation Section
28
- To insure proper drainage, locate the highest
vertical position, no more than 17 ft (5.2 m) at
460 VAC, and run the drain hose on a
downward slope at a minimum rate of 1/4 in
(6.25 mm) per foot.
< NOTE >
The condensate pump maximum lift is 17 ft (5.2 m) at 460 VAC. Please check the drainage
performance after installation. It is important that the drainage line from the condensate pump is
free of kinks and is not pinched. Power fluctuation or low voltage could result in incorrect drainage.
I001920
Condensate
Pump
Grommet
1/4 in (6.25 mm)
Taper Per Foot
17 ft (5.2 m) Max