Operation Section

22

6.3 Transformer

• A dry-type transformer rated 5 KVA is equipped

within the unit to provide step down voltage

from 460 V single phase to 230 V single phase.

• The terminal connection of the primary side of

the transformer are labeled H1, H2, H3, and

H4. Terminals H2 and H3 are shorted together

to provide a series connection for 460 V

application. Terminals H1 and H4 are

connected to 460 V power source to supply

power to secondary side.

• Terminals X2 and X3 of the secondary side are

also shorted together to provide 230 V output

between terminals X4 and X1.

Specifications:

Distribution transformer

- Type: Dry type

- Rated VA: 5000 VA

- Power Requirement: 1 PH, 60 Hz

- Primary Voltage: 460 V

- Secondary voltage: 230 V

I001954

Primary
(460 V)

Coil

<Wiring Diagram>

Secondary
(230 V)

Short Circuit

Short Circuit

H3 H2

H4

X1

X2 X3

X4

H1

Terminal Block
(Secondary)

Terminal Block
(Primary)

Advertising