Repair Section

39

(2) Unit does not start (operate)

< NOTE >

• In this case, there is a possibility of safety device activating due to the clogged air filter. So make

sure to first clean the air filter and then start up again to confirm if the problem lies with the air filter.

• Check the installation site for operating temperature and installation space (unobstructed airflow).

• Check the phase sequence of the power source.

If the phase sequence is reversed, the control panel display, and reverse phase protector LED in

the control box turn off.

Possible Cause

Remedy

Checking Area

Cause

Does not

operate at

all

Control

Panel

display turns

off.

1. Voltage.

Power failure.

Repair power.

2. Phase sequence of the

power source.

Phase sequence is

reversed.

Change any 2 of the 3 wires

for power source wires.

3. Ground fault breaker trip.

Ground fault or defective

ground fault breaker.

Repair ground fault section.

Reset or repair breaker.

4. Fuse.

Fuse blown.

Repair shorting section.

Replace fuse on the relay

board.

Replace fuse of the

transformer secondary side.

5. Transformer.

Defective transformer.

Replace transformer.

6. Reverse phase protector.

Open circuit or insufficient

contact.

Replace reverse phase

protector.

Symptom