MovinCool Office Pro 63 Service Manual User Manual

Page 38

Advertising
background image

Repair Section

38

Symptom

Possible Cause

Remedy

Checking Area

Cause

Air volume

normal

Compressor

operates.

1. Usage conditions

(high temperature).

Operation near usage limits.

Review the installation

place.

2. Dirt in condenser or

evaporator.

Insufficient heat exchange.

Clean fins.

3. Frost in refrigeration cycle.

Clogging at the frost section. Replace clogged section.

4. No temperature difference

between evaporator and

condenser.

Insufficient refrigerant.

Check the leaking part,

then repair and charge

refrigerant.

Compressor

does not

operate.

1. Compressor coil resistance.

(0 ohm or

∞ ohm)

Short or open circuit.

Replace compressor.

(In case of short, check

the compressor relay.)

2. Compressor relay.

Open circuit or insufficient

contact.

Replace compressor

relay.

3. Compressor relay on the

relay board.

Open circuit or insufficient

contact.

Replace relay board.

4. Voltage.

Low voltage.

Repair power.

Insufficient

air volume

No air.

1. Coil resistance of fan motor.

(0 ohm or

∞ ohm)

Short or open circuit.

Replace fan motor.

2. Fan on-off relay on the relay

board.

Open circuit or insufficient

contact.

Replace relay board.

3. Fan HI/LO change relay on

the relay board.

Open circuit or insufficient

contact.

Replace relay board.

Insufficient

air volume.

1. Air filter.

Clogged air filter.

Clean air filter.

2. Evaporator.

Clogged evaporator or

crushed fins.

Repair and clean fins or

replace it.

3. Duct connection state.

Improper connection.

Repair duct connection.

4. Fan motor.

Insufficient rotation.

Replace motor.

5. Transformer.

Low voltage.

(Secondary side)

Replace transformer.