Repair Section

36

Indication of service

code

Press ON/OFF and

U buttons

simultaneously for 3 sec. Indication

contents is as follows.

1) See page 36 and 37.

2) Press ON /OFF button.

Change model setting

For installing new controller PCB, if

a different model name appears

when the unit is reset or turned on,

change model name according to

the correct procedure.

1) While pressing

U and V

buttons, plug the power cord.

<Condition>

LCD indicates current setting

model name and buzzer sounds.

2) After setting the model type by

pressing

U and V button, 

unplug the unit.

Activation of high

pressure switch

When high pressure switch

(connected to J104) activates

(=J104 input turns to open) 3 times

in 24 h, “HP” is indicated and signal

output (J106) turns on.

When it activates 10 times in 24 h,

“FAIL HP” is indicated and buzzer

sounds.

Find the cause of high pressure to

address it.

Check the following.

Ambient air temperature

(65 °F (18.3 °C),

50

%

RH

95 °F (35 °C), 60 %RH)

Air filter (if dirty, wash up.)

Condenser fan motor (if not

working, replace.) Defect of high

pressure switch (if switch is open

when unit is off, replace switch.)

Reset the system.

To RESET: Press ON/OFF and

HI/LO buttons on the control box

simultaneously for 5 sec.

LCD Display

Description

Condition

Reset/Remedy

LCD

DF

FZ

OD

Description

Value

Defrost status

Evap. out pipe
temperature

26

109F

(“26”

“X9”)

Outdoor
temperature

0 (“00”)

TU

AM

F

SET TEMP

HI

ON

COOL

FAN