Operation Section

24

(3) Relay board

• The relay board receives signals and outputs

from the control board that contains a

microprocessor. The relay board contains the

compressor, fan on and fan mode (speed)

relays.

• It also contains a step-down transformer that

converts the line voltage (230 VAC) to 12 V.

• This 12 V is then converted from AC to DC and

used for relay coil activation. The 12 V (DC)

power is sent to the control panel assembly where it is further reduced to 5 V for the system logic.

• The relay board also contains the DIP switch.

• The DIP switch is used to change the fan mode operation from stop to operate and change both

the set point and room temperature display from Fahrenheit to Celsius.

< NOTE >

The relay board must be serviced as a complete assembly. It has only one serviceable

component, the fuse. (see below)

(4) Relay board fuse

• This fuse provides protection against damage

to the step-down transformer. It must be

replaced with the exact type of fuse or an

equivalent.

Specifications:

- 2/10 A, 250 V

CAUTION

Failure to use the exact type of fuse could result in damage to the unit and/or to components. It

could also void the warranty of the unit.

I001772

Dip Switch

<Dip Switch>

Fan Mode Control
Switch
(STOP

OPERATE)

Temperature Scale
Display Switch
(°C

°F)

I001773

Fuse

<Relay Board>