Operation Section

27

6.7 Condensate Pump

• The Office Pro 63 is equipped with a condensate pump, which collects the water that forms on

the evaporator during normal cooling operation and eliminates the need for a drain tanks.

- When the water collects to level (A) in the

pump reservoir, the condensate pump begins

to operate and discharge the water. During

condensate pump operating period the

compressor cycles off.

- When the water level drops below level (B),

the condensate pump stops and compressor

restarts after delay time has expired.

< NOTE >

• If for any reason the water level exceeds that of level (A) in the pump reservoir, an overflow drain

switch stops the compressor operation.

• If the fan mode control DIP switch has been set from the cool to the stop position, the fan also

turns off while the condensate pump is discharging the water.

I001918

Cover

Motor Fan

Mounting Ear

Main Control Float

Reservoir

3/8 in (9.53 mm) I.D.
Drain Outlet Spout
with Check Valve

1 in (25.4 mm)
Inlet Drain Hole

I001919

A

B

Advertising