8.11 Inspection of Transformer

• Measure resistance across the terminals of the

transformer.

(All terminals must be disconnected from the

unit.)

• Between terminals (at 77 °F (25 °C))

- H1-H4 Approx. 0.3 ohm

- X1-X4 Approx. 0.3 ohm

- X1-H4 Approx. Open

• If the measured resistance is not equal to these

standard values, replace the transformer.

8.12 Inspection of Wiring Connection

• Refer to the Wiring Diagrams on page 19 and check for connection of each wire.

8.13 Inspection of Thermistor

• Using an Ohm-meter, check the resistance value across the 2-pin connector. At normal

temperature (77 °F (25 °C)) either thermistor (room or freeze) should measure approximately

10 k ohm.