background image

Repair Section

42

(4) Abnormal noise or vibration

• To prevent abnormal noise or vibration, carefully determine the source of the problem and come

up with proper countermeasures to solve the problem so that it does not occur again.

< NOTE >

Internal dry-type distribution transformer may produce a humming noise up to 31 dB (A) at

maximum operated voltage (506 V) during stand-by state.

7.4 Basic Inspection

• Perform the following inspection before disassembly.

(1) Inspection of plate fins

• To inspect the plate fins of either the evaporator

or condenser, the air filter must be removed.

After removal of the air filters, inspect the plate

fins for any dirt, dust, lint, or debris that may

have caused insufficient cooling performance

of the unit. If cleaning of the fins is necessary, it

is recommended that this service be performed

by a qualified service technician.

(2) Examination of operating environment

• Operating environments can vary depending on location, climate and surrounding conditions.

Installation location also can cause operational problems. Consult your reseller concerning

operational environment requirements.

Symptom

Possible Cause

Remedy

Checking Area

Cause

Abnormal noise or

vibration.

1. Fan.

Fan interference.

Repair interfering section.

Fan deformation.

Replace fan.

2. Compressor fixing nuts.

Looseness of nuts.

Tighten nuts further.

3. Transformer fixing nuts.

Looseness of nuts.

Tighten nuts further.

4. Piping.

Pipe interference.

Repair interfering section.

5. Panel fixing screws.

Looseness of screws.

Tighten screws further.

I001780