Repair Section

35

Defect (short or open)

of freeze protection

thermistor

When freeze protection thermistor

(connecting to J102) becomes short

or open.

(Signal output (J106) turns on.)

Disconnect and reconnect the

freeze protection thermistor.

If it doesn’t work, then change it.

Show running hours

Press ON/OFF and

V

buttons

simultaneously for 3 sec, total

operation hours of compressor is

indicated by 6-digit (hours).

Example in left: 807 h

After 5 sec., display goes back to

normal mode.

Show LCD and LED

all on mode

Press HI/LO and

U buttons

simultaneously for 3 sec.

(To check LCD segments and LED

display.)

After 5 sec., display goes back to

normal mode.

Key lock mode (LCD

displays “LOCKED”.)

Press ENTER and SET CLOCK

buttons simultaneously for 5 sec.

Press ENTER and SET CLOCK

buttons simultaneously for 5 sec

again to cancel the key lock mode.

Indication of model

name

Press ENTER and SET CLOCK

buttons simultaneously for 5 sec or

turn on.

Reset to normal display

automatically after 5 sec.

Detection of unit stop

signal from fire alarm

system

Press input signal from fire alarm

becomes on.

(Unit stops, output signal (J106)

turns on and buzzer sounds.)

1) After input signal turns off.

2) Reset the system.

To RESET: Press ON/OFF and

HI/LO buttons on the control box

simultaneously for 5 sec.

LCD Display

Description

Condition

Reset/Remedy

F

SET TEMP

HI

ON

COOL

FAN

F

SET TEMP

HI

ON

COOL

FAN

START

STOP

CLOCK

MO TU WE TH FR

AM

F
C

F
C

PROGRAM

LOCKED

ON

PM

SA SU

SET TEMP

ROOM TEMP

HI

LO

ON

OFF

COOL

FAN

TU

AM

F

LOCKED

SET TEMP

HI

ON

COOL

FAN

Advertising