9.2 Removal of Refrigeration Cycle Components

CAUTION

• Before any refrigeration cycle component can be replaced, it is necessary to recover the

refrigerant using standard recovery procedures and equipment.

• To prevent oxidation, dry nitrogen should be conducted (flow rate 0.27 gal/min (1 L/min)) through

the pinch-off tube during any brazing operation.

• During any component replacement involving brazing, shield nearby parts with a steel plate, etc.,

to protect them from the flame.

• Evaporator

• Capillary tube

• Condenser

• Compressor

• High Pressure Switch

< NOTE >

When replacement of the compressor, attach the two pipes (Pipe 1, Pipe 2) which are packaged

in Compressor Assy as following figure.

I002170

Compressor

A & F
A & B
C & D
C & E

Condenser
Capillary Tube
Evaporator

Part to Replace

Disconnect At

A

B

F

E

D

C

Pipe 1

Pipe 2