ONICON F-2600 User Manual

Page 18

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

F-2600 & F-2700 Vortex Flow Meter Manual 02/15 - 0808-7 / 19204

Page 18

1.3.2 Line Size / Process Connections / Materials

The in-line model is built for line sizes ½" through 4" wafer or ½" through 8" flanged
design using ANSI 150, 300, 600, PN16, 40, or 64 class flanges.

The insertion model can be used in line sizes 2" and greater and is built with a packing
gland design using 2" NPT, or 2" flanged connections (ANSI 150, 300, 600, PN16, 40, or 64
class flanges). The packing gland design can be ordered with a permanent or removable
retractor.

The standard in-line model is built with 316L stainless steel, A105 carbon steel and
Hastelloy C-276 versions are available via special order. The insertion model is built with
316L stainless steel.

1.3.3 Flow Meter Electronics

The flow meter electronics are available mounted directly to the flow body, or mounted
remotely. The electronics housing may be used indoors or outdoors, including wet
environments. Available input power options are: DC loop powered (2-wire), DC powered,
or AC powered. Three analog output signals are available for your choice of three of the
five process variables: mass flow rate, volumetric flow rate, temperature, pressure or fluid
density. A pulse output signal for remote totalization and BACnet, MODBUS or HART
communications is also available.

Each meter includes a local 2 x 16 character LCD display housed within the enclosure.
Local operation and reconfiguration is accomplished using six pushbuttons operated via
finger touch. For hazardous locations, the six buttons can be operated with the electronics
enclosure sealed using a hand-held magnet, thereby not compromising the integrity of the
hazardous location certification.

The electronics include nonvolatile memory that stores all configuration information. The
nonvolatile memory allows the flow meter to function immediately upon power up or after
an interruption in power. All flowmeters are calibrated and configured for the customer’s
flow application.

Advertising
This manual is related to the following products: