ONICON F-2600 User Manual

Page 85

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

F-2600 & F-2700 Vortex Flow Meter Manual 02/15 - 0808-7 / 19204

Page 85

Registers

Variable

Data Type

Units

Function Code Addresses

65100-65101 Serial number

unsigned long —

03, 04

30525-30526 Totalizer

unsigned long display units 03, 04

524-525

32037-32042 Totalizer units

string

03, 04

2036-2041

30009-30010 Mass flow

float

display units 03, 04

8-9

30007-30008 Volume flow

float

display units 03, 04

6-7

30005-30006 Pressure

float

display units 03, 04

4-5

30001-30002 Temperature

float

display units 03, 04

0-1

30029-30030 Velocity

float

ft/sec

03, 04

28-29

30015-30016 Density

float

display units 03, 04

14-15

30013-30014 Viscosity

float

cP

03, 04

12-13

30031-30032 Reynolds number float

03, 04

30-31

30025-30026 Vortex frequency float

Hz

03, 04

24-25

34532

Gain

char

03, 04

4531

30085-30086 Vortex amplitude float

Vrms

03, 04

84-85

30027-30028 Filter setting

float

Hz

03, 04

26-27

Table 3. Register Definitions

The following registers are available with the energy meter firmware:

Registers

Variable

Data Type

Units

Function Code Addresses

30527-30528 Totalizer #2

unsigned long display units 03, 04

526-527

32043-32048 Totalizer #2 units string

03, 04

2042-2047

30003-30004 Temperature #2

float

display units 03, 04

2-3

30011-30012 Energy flow

float

display units 03, 04

10-11

The following registers contain the display units strings:

Registers

Variable

Data Type

Units

Function Code Addresses

32007-32012 Volume flow units

string

03, 04

2006-2011

32001-32006 Mass flow units

string

03, 04

2000-2005

32025-32030 Temperature units

string

03, 04

2024-2029

32019-32024 Pressure units

string

03, 04

2018-2023

32031-32036 Density units

string

03, 04

2030-2035

32013-32017 Energy flow units

string

03, 04

2012-2017

Function codes 03 (read holding registers) and 04 (read input registers) are the only codes
supported for reading these registers, and function codes for writing holding registers are
not implemented. We recommend that the floating point and long integer registers be read
in a single operation with the number of registers being a multiple of two. If this data is
read in two separate operations, each reading a single 16-bit register, then the value will
likely be invalid.