F-2600 & F-2700 Vortex Flow Meter Manual 02/15 - 0808-7 / 19204

Page 60

3.3.3 Display Menu

Password

ENTER

Display

Menu

Cycle Time (sec)

0

ENTER

Run Mode

Number of Digits

2

MF Vf Te Pr De T

Y or N

A1 A2 A3 Fl Dt E

Y or N

If Cycle Time is set to zero, manual advance is required.

Used to set the number of digits displayed after the decimal point.

MF = Mass Flow

Vf = Volume Flow

Te = Temperature

Pr = Pressure

De = Density

T = Total

A1 = Alarm 1 Status

A2 = Alarm 2 Status

A3 = Alarm 3 Status

Fl = Fluid

Dt = Density

For each parameter:

Select Yes to view parameter in Run Mode.

Select No to hide parameter in Run Mode.

Display TC (sec)

1

TC = Display Time constant, used to smooth display.

* E = Energy

*

Energy Meters Only

Use

keys to access menus

Use the Display Menu to set the cycle time for automatic screen sequencing used in the
Run Mode, change the precision of displayed values, smooth the values or enable or
disable each item displayed in the Run Mode screens.

Example for Changing a Run Mode Display Item

The following shows how to remove the temperature screen from the Run Mode screens.
Note: All outputs are disabled while using the Set-up Menus.
1. Use

⇐ ⇒ keys to move to the Display Menu.

2. Press

⇓ key until Mf Vf Pr Te De T appears.

3.

Press ENTER to select. Press ⇒key until the cursor is positioned below Te.

4. Press

⇓ key until N appears. Press ENTER to select.

5.

Press EXIT and then ENTER to save changes and return to the Run Mode.