Warning – ONICON F-2600 User Manual

Page 71

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

F-2600 & F-2700 Vortex Flow Meter Manual 02/15 - 0808-7 / 19204

Page 71

SECTION 4.0: SERIAL COMMUNICATIONS

4.1 HART COMMUNICATIONS

The HART Communications Protocol (Highway Addressable Remote Transducer Protocol) is a
bidirectional digital serial communications protocol. The HART signal is based on the Bell 202
standard and is superimposed on 4-20 mA Output 1. Peer-to-peer (analog / digital) and multi-drop
(digital only) modes are supported.

4.1.1 WIRING

The diagrams below detail the proper connections required for HART communications:

Loop Powered Meter Wiring

LOOP

POWER

+

-

FREQ OUT

PULSE OUT

-

-

+

+

OPTIONAL BACKLIGHT POWER +

-

R load,

250 ohm

minimum

+

_

DC

Power

Supply

Remote Connection

for Communicator

Current

Meter

Field Connection

for Communicator

Vortex Meter

Figure 50. Loop Powered Meter Wiring (HART)

!

WARNING

Place controls in manual mode when making configuration changes to the vortex meter.

Advertising
This manual is related to the following products: