4.3 BACnet MS/TP Communications

4.3.1. BACnet MS/TP Description

The BACnet Master-Slave/Token-Passing (MSTP) driver implements a data link protocol that
uses the services of the RS-485 physical layer. The MS/TP bus is based on BACnet standard
protocol SSPC-135, Clause 9. BACnet MS/TP protocol is a peer-to-peer, multiple master
protocols based on token passing. Only master devices can receive the token, and only the
device holding the token is allowed to originate a message on the bus. The token is passed from
master device to master device using a small message. The token is passed in consecutive order
starting with the lowest address. Slave devices on the bus only communicate on the bus when
responding to a data request from a master device.

4.3.2. Baud Rates on the MS/TP Bus

An MS/TP bus can be configured to communicate at one of four different baud rates. It
is very important that all of the devices on an MS/TP bus communicate at the same baud
rate. The baud rate setting determines the rate at which devices communicate data over
the bus. The available baud rate settings available on F-2600 and F-2700 Flow Meters are
9600, 19200 and 38400.

4.3.2.1. Baud Rate and MAC address configuration

1. Power on the meter
2. Press Enter to go configuration menu
3. Give the factory password 16363 (Use Up and Down arrows to enter the digits)
4. Navigate to Diagnostics menu
5. Press Enter and press right button immediately
6. Navigate to Config Code screen by continuous pressing down button
7. After reaching config code screen, press right to navigate to Comm. Type screen
8. Change the comm. Type to “Modbus” and press Enter

Note: Modbus will enable Baud Rate and MAC address screens

9. Press Exit twice to reach Diagnostics menu back
10. Navigate to Output Menu by using right or left arrow buttons
11. Press Down button and reach Baud Rate and MAC address screens
12. Change the required settings and press Exit & Enter buttons to save the configuration
13. Do steps from b to g, and change the comm. Type as Hart.
14. Reboot the device by power off and on.

Note:
a. Baud rates are 9600, 19200 or 38400
b. MAC address range is 0-127

4.3.3. Supported BACnet Objects

A BACnet object represents physical or virtual equipment information, as a digital input
or parameters. ONICON F-2600 and F-2700 Flow Meters present the following object
types:

a. Device Object
b. Analog Input
c. Binary Input
d. Binary Value

Each object type defines a data structure composed by properties that allow the access
to the object information. The below table shows the implemented properties for each
Vortex Mass Flow Meters object type.