2.7.7 Optional Input Electronics Wiring

The meter has two optional input wiring terminals. These can be used to input a remote
or second RTD input in the case of an energy monitoring meter, for the input of a remote
pressure transducer, to pass a contact closure or for a remote density measurement to
name a few. In any case, the wiring diagram will be included with the meter if any of the
options are specified. Otherwise, the optional terminal blocks will be left blank and
non-functional.

Option 2

Option 1

1 2

3 4 5

1

2 3 4 5

2.7.8 OPTIONAL ENERGY EMS RTD INPUT WIRING

Option 2

Option 1

1 2

3 4 5

1

2 3 4 5

R = 1000 ohm

Red Red Black Black

Figure 44. Optional Energy EMS RTD Input Wiring

The recommended customer supplied second RTD is a Class A 1000 ohm 4-wire platinum
RTD. If a second RTD is not being used, then the factory supplied 1000 ohm resistor needs
to be installed in its place.