ONICON F-2600 User Manual

Page 39

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

F-2600 & F-2700 Vortex Flow Meter Manual 02/15 - 0808-7 / 19204

Page 39

2.6.6 Remote Electronics Wiring

The remote electronics enclosure should be mounted in a convenient, easy to reach
location. For hazardous location installations, make sure to observe agency requirements
for installation. Allow some slack in the interface cable between the junction box and the
remote electronics enclosure. To prevent damage to the wiring connections, do not put
stress on the terminations at any time.

The meter is shipped with temporary strain relief glands at each end of the cable.
Disconnect the cable from the meter’s terminal block inside the junction box - not at the
remote electronics enclosure. Remove both glands and install appropriate conduit entry
glands and conduit. When installation is complete, re-connect each labeled wire to the
corresponding terminal position on the junction box terminal block. Make sure to connect
each wire pair’s shield. Note: Incorrect connection will cause the meter to malfunction.

RED 1

BLK 1

BLK 2

RED 2

SHLD 1&2

SENSOR V1

VORTEX

GND

PWR

SENSOR V2

SHIELD

Figure 24. Loop-Powered Volumetric Flowmeter Junction Box Sensor Connections

!

i

!

IMPORTANT NOTE

Numeric code in junction box label matches wire labels.

Advertising
This manual is related to the following products: