Danger, Online power – OnLine Power Protector 3 User Manual

Page 37

Advertising
background image

OnLine Power

5-4

5.4.2 Periodic Testing of UPS

The UPS Unit should be manually exercised on a periodic basis (once every three months, for example).
This forces the UPS unit to transfer to the battery and return to main power. This process activates self-
diagnostic testing which may reveal conditions that require attention.

5.4.3 Maintaining the Batteries

Danger!

BATTERY CIRCUIT BREAKER OPERATES AT THE RATED BATTERY
VOLTAGES AT ALL TIMES. TRIPPED BATTERY CIRCUIT BREAKER
INDICATES A SERIOUS PROBLEM THAT MAY RESULT IN SERIOUS INJURY
OR DAMAGE TO THE EQUIPMENT IF CLOSE THE CIRCUIT BREAKER
WITHOUT KNOWING WHY IT FAILED. CHECK SHORT IN BATTERY OR CALL
ONLINE POWER CUSTOMER SERVICE AND SUPPORT FOR ASSISTANCE AT

1-800-PWR-SRVC.

Danger!

THE BATTERY ELECTROLYTE IS A DILUTED SULFURIC ACID THAT IS
HARMFUL TO THE SKIN AND EYES. IT IS ELECTRICALLY CONDUCTIVE AND
CORROSIVE. WEAR FULL EYE AND HAND PROTECTION ALONG WITH
PROTECTIVE CLOTHING. IF THE ELECTROLYTE CONTACTS THE SKIN,
WASH IT OFF IMMEDIATELY WITH WATER. IF ELECTROLYE CONTACTS
THE EYES, FLUSH THOROUGHLY AND IMMEDIATELY WITH WATER. SEEK
IMMEDIATE MEDICAL ATTENTION. SPILLED ELECTROLYTE SHOULD BE
WASHED DOWN WITH A SUITABLE ACID NEUTRALIZING AGENT. ONE
COMMON PRACTICE IS TO USE A SOLUTION OF APPROXIMATELY ONE
POUND (500 GRAMS) OF BICARBONATE OF SODA TO APPROXIMATELY
ONE GALLON (4 LITERS) OF WATER. THE BICARBONATE OF SODA
SOLUTION SHOULD BE APPLIED TO THE SPILL UNTIL EVIDENCE OF
CHEMICAL REACTION (FOAMING) HAS CEASED. THE RESULTING LIQUID
SHOULD BE FLUSHED WITH WATER AND THE AREA DRIED.

Danger!

DO NOT DISPOSE OF A BATTERY OR BATTERIES IN A FIRE. THE
BATTERIES MAY EXPLODE CAUSING DEATH OR SERIOUS INJURY.

Advertising